The Surefit Anchor is a universal throughbolt expansion anchor available in either electro-galvanised steel or stainless steel. The unique expansion segment means that the anchor can be used for "stress-free" applications in the same way as either a resin or undercut anchor, for close edge and axial spacing.
The Surefit Anchor is suitable for concrete but can also be used in solid Masonry.
No special drill-bit or setting tool is required for installation and the anchor can be completely removed after installation if required.
Supplied with Sleeve, Washer and Bolt
| 1. | Drill 12 mm or 16 mm hole to required depth |
| 2. | Remove dust and debris from hole |
| 3. | Position attachment in the correct location to the drilled hole e.g. Sikla Channel, end plate or bracket component. |
| 4. | Using a hammer, drive the anchor through the fixture into the base material until both fixture and anchor are bearing firmly against base material. |
| 5. | Observing the recommended installation torque, tighten the nut until the required toque has been reached. The anchor may be immediately loaded. |
|
Type | M12 Tension F | M12 Shear V | M16 Tension F | M16 Shear V |
|---|---|---|---|---|
| Ultimate load in concrete 30 N/mm2 (kN) | 14,20 | 11,50 | 30,50 | 34,30 |
| Characteristic load in concrete 30 N/mm2 (kN) | 13,80 | 9,80 | 25,80 | 28,90 |
| Permissible load in concrete 30 N/mm2 (kN) | 4,60 | 3,30 | 8,60 | 9,60 |
| Type | M12 | M16 |
|---|---|---|
| Permissible bending moment (Nm) | 77,90 | 155,30 |
| Recommended embedment depth (mm) | 50 | 90 |
| Min. Axial spacing (mm) | 110 | 225 |
| Min. Edge spacing (mm) | 60 | 110 |
| Min. base material thickness (mm) | 90 | 175 |
| Nominal diameter of drill bit (mm) | 12 | 16 |
| Min. drill hole depth (mm) | 60 | 100 |
| Installation torque (Nm) | 15 | 50 |
| Spanner / socket size (standard head) (mm) | 10 | 17 |
| Spanner / socket size (modified head) (mm) | 13 | n/a |
All load values are taken from tests conducted for the ETA submission. Avaiable in "super stainless" DIN 1.4529 for highly corrosive environments. Due to controlled expansion zone of anchor upon installation, anchor may be used within majority of brickwork and blockwork base materials.
Large washer (nominal 20 mm OD) for spreading the load when used to fix through the slots of Sikla Channel. M6 or M8 head in gr 8.8 high tensile steel allows for easy 10 mm or 13 mm A/F box-spanner or socket access into Channel profile without clashing with openface of Channel sides.
Compatibility with Sikla components (as a through-fix to base material)
European Technical Approval (pending)
Fire tested
| Type | Thread | Head | A/F [mm] |
Fixture Thickness [mm] |
Total length [mm] |
W [kg] |
Quantity/ [pack] |
Part- No. |
|---|---|---|---|---|---|---|---|---|
| 12 / 10 | M6 | M6 | 10 | 10 | 60 | 0.035 | 50 | 266526 |
| 12 / 10 | M6 | M8 | 13 | 10 | 60 | 0.038 | 50 | 266527 |
| 16 / 10 | M10 | M10 | 17 | 10 | 100 | 0.228 | 25 | 266528 |