Group: 1727
For wall, ceiling and floor installation for mounting elements in M&E services.
The nominal loads mentioned shouldn't be exceeded. Permissible anchor values may restrict the application.
| Version / Type | Tension [kN] | Perm. bending moment* [Nm] | Max. lever arm [mm] | Schweiß- verfahren |
|---|---|---|---|---|
| Stabil M8 | 3.0 | 8.8 | 150 | R |
| Stabil M10 | 3.0 | 17.2 | 200 | R |
| Stabil M12 | 3.0 | 29.6 | 300 | R |
| Stabil M16 | 4.5 | 70.3 | 300 | M |
| Stabil R 1/2" | 4.5 | 95.0 | 350 | M |
| Stabil R 3/4" | 6.2 | 180.0 | 450 | M |
R = Widerstandsschweißung
M = Schmelzschweißung
| * | Limitation caused by the Mounting Plate or the loading capacity of the grub screw or of the threaded tube. σperm ≤ 160 N/mm2 fperm < 5 mm |
| Material: | Stainless steel A4 |
| Type | Dimension L x W x Th [mm] |
Elongated hole d x a [mm] |
Centre distance l [mm] |
W [kg] |
Quantity [pack] |
Part- No. |
|---|---|---|---|---|---|---|
| Stabil M8 | 120 x 40 x 4 | 11 x 25 | 80 | 0.14 | 50 | 107608 |
| Stabil M10 | 120 x 40 x 4 | 11 x 25 | 80 | 0.14 | 50 | 107617 |
| Stabil M12 | 120 x 40 x 4 | 11 x 25 | 80 | 0.14 | 50 | 107626 |
| Stabil M16 | 120 x 40 x 4 | 11 x 25 | 80 | 0.16 | 50 | 107635 |
| Stabil R 1/2" | 120 x 40 x 4 | 11 x 25 | 80 | 0.16 | 50 | 107644 |
| Stabil R 3/4" | 120 x 40 x 4 | 11 x 25 | 80 | 0.17 | 50 | 107653 |